Protec Equipment Resources
   Contact Us: 866.352.5550
    

Monitor Power Quality with 8-Channel Dranetz HDPQ Xplorer Analyzer

Posted by Protec Tech Team on

Dranetz HDPQ Xplorer Power Quality AnalyzerThe Dranetz HDPQ Xplorer Power Quality Analyzer offers top of the line monitoring capabilities, measuings to all current industry standards, including IEC 61000-4-30 Class A, IEC 61000-4-7, IEEE 1159, IEEE 519, IEEE 1459, and more.

With its high speed transient data capture (1 microsecond/channel) capabilities, this 8-channel analyzer simultaneously captures and characterizes thousands of parameters, by using a range of standard and customizable operating modes.

 

Dranetz HDPQ General Specifications

Size (HxWxD) in inches and cm
Weight: 2 kg, 4.3lbs
Operating temperature: 0 to 50 deg C
Storage temperature: -20 to 60 deg C
Humidity: 0-95% non condensing
Clock accuracy and resolution
Internal: +/- 1 sec/day at 25deg C
NTP: +/-10 msec
GPS: +/-1 msec
AC Adapter: 100-240Vac 50/60Hz
Battery capacity and charge time: 3 hours run time on full charge
Memory size: 4GB
Display: 7” WVGA color graphic, Icon based touch LCD, LED Backlit

 

Measured Parameters

(4) Differential Voltage: 512 s/c (1MHZ for HS Trans.), 16 bit resolution

  • 0-1000Vrms, AC/DC, +/- 0.1% reading +/- 0.05% FS
  • IEC 61000-4-30 Class A: 40-1000Vrms, ±0.1 % of Udin, range of 10% ~ 150% of Udin
  • Transients – High Speed: 10-2000Vpk, +/- 10% of reading, +/- 0.5%FS
  • Transients – rms: 0-1400Vpk, ±0.2 % of Udin

(4) Current (rms): 512 s/c (1MHZ for HS Trans.), 16 bit resolution

  • Range probe dep., AC/DC, +/- 0.1% reading +/- 0.05% FS, ±0.2 % of Udin
  • Transients – High Speed: Range probe dep., 10% of Reading, +/- 0.5%FS
  • Transients – rms: Range probe dep., ±0.2 % of Udin

Frequency: 10 sec window

  • 16-25Hz, 41-69Hz, +/- 0.01Hz

 

Calculated Parameters

Power/Energy – 1 Second sampling
Real Power (W) – P: meets 0.2S requirements, range probe dep.
Apparent Power (VA) – S: meets 0.2S requirements, range probe dep.
Reactive Power (var) – Q: meets 0.2S requirements, range probe dep.
Power Factor (W/VA) -”true” 1 to 0 to 1
Displacement PF 1 to 0 to 1
Demand (in W): meets 0.2S requirements, range probe dep.
Energy (in Wh): meets 0.2S requirements, range probe dep.

Distortion – 200ms, 3 sec, 10 min windows
Vthd: 0-100%, +/- 5% for V>=1% Vnom,
V Ind Harm: DC, 2-127, +/- 5% for V>=1% Vnom
Ithd: 0-100%, +/- 5% for V>=1% Vnom,
I Ind Harm: DC, 2-63, +/- 5% for V>=1% Vnom

Misc.
Pst – 10 minutes: 0.2-10, +/- 0.05 @ Pst=1
Plt – 2 hours: 0.2-10, +/- 0.05 @ Pst=1

 

Standards Compliance

Power Quality IEC 61000-4-30 Class A: Edition 2 (2008)
IEEE 1159: 2009

Power
IEEE 1459: 2000

Harmonics
IEC 61000-4-7 Class 1: Edition 2 (2008)
IEEE 519: 2014

Voltage Flicker
IEC 61000-4-15: Edition 2 (2010) IEEE 1453: 2011

Compliance/Testing
EN 50160: 2010

Related electrical test equipment available for rent from Protec:

Amprobe DM-III Multitest Power Quality Recorder

Fluke 1750 Three Phase Power Recorder

Fluke 1735 Three-Phase Power Quality Logger

This electrical test equipment is available for rent, lease, or purchase from Protec Equipment Resources. We are here to help you with your testing equipment needs.

Protec's Calibration Lab offers accurate and affordable calibration services for all makes and models of electrical test and measurement equipment. Contact us today for a quote.